Overview
The 1747-BSN Backup Scanner Module provides a high-speed communication
channel between two modular SLC 500™ (5/02 or higher) processors. The 1747-
BSN backup system uses a set of modules, with one or more 1747-BSN modules
residing in the primary system and one or more complementary modules in the
secondary or backup system. The primary system controls the operation of
remote I/O, while the secondary system monitors www.abb-drive.com communications via the highspeed
serial link (HSSL) and is available to take over control in the event of a
fault in the primary system.
Configuration Errors
The module reports the following configuration errors by flashing the fault LED:
• two 1747-BSN modules are configured with the same address
• LSL addresses are not consecutive (addresses must be numbered 0, 1, 2,etc.)
• last LSL switch is not set in the last module in the link
• last LSL switch is set in a module that is not the last in the link, or
• primary and secondary modules do not have the same configuration settings
(secondary module shows the configuration error)
Switchover Conditions
The 1747-BSN module transfers control from the primary to the secondary
processor (switchover) if one of the following fault conditions occurs in the
primary system:
• power failure
• major fault in the processor
• 1747-BSN module fault
• primary processor mode change from Run to Program
Note: In order for switchover to occur, both primary and
secondary modules must be working without faults prior
to the event that triggers the switchover.