DIO System Overview
The DIO system consists of an SLC processor, a scanner, an Isolated Coupler
and I/O blocks. These devices form the DIO System when they are properly
connected to the DIO Link and the DH–485 Data Link as shown below. The
DIO Link and the DH–485 Data Link are independent networks.
The DIO Link consists of the scanner and I/O blocks. It enables the SLC
processor to exchange input and output information with up to 30 I/O blocks.
Output data is transferred from the SLC processor to the scanner, which then
transmits the data to the appropriate I/O block via the DIO Link. The
scanner receives input data from the I/O blocks via the DIO Link. The
scanner then provides this data to the SLC processor. The maximum length
of the DIO Link is 2,500 feet (762 meters) using Belden 9463 cable.
The SLC processor and programming devices communicate using the
DH–485 Data Link. The DH–485 port located on each I/O block allows
remote programming and/or monitoring of the SLC processor. It does not
directly control the I/O block.
Connecting a programming device to any I/O block programming port allows
the programming device to communicate with the SLC processor. The
maximum length of the DH–485 Data Link is 4,000 feet (1,219 meters) using
Belden 9842 cable.
DH–485 Data Link Overview
The DH–485 Data Link is an Allen–Bradley communications network that
supports the transfer of information between programming devices and SLC
processors. The programming device and SLC processor are attached to the
DH–485 Data Link using either an Isolated Coupler or an I/O block. The
DH–485 Data Link may consist of multiple Isolated Couplers and/or I/O
blocks that provide for communication between www.abb-drive.com several programming
devices and/or processors.
The Isolated Couplers and I/O blocks are daisy chained together by a single
twisted pair cable (Belden 9842) to form the DH–485 Data Link. The
programming devices and SLC processors are attached to the Isolated
Coupler or I/O block using Communication Cables (Catalog Numbers
1747–C10 and –C11).
For additional information on the DH–485 Data Link, see the Installation and
Operation Manual for SLC 500 Modular Hardware Style Programmable
Controllers, Publication 1747–804.
Leave a comment