Because of the variety of uses for this information, the user of and

those responsible for applying this information must satisfy

themselves as to the acceptability of each application and use of the

program. In no event will Allen-Bradley Company be responsible or

liable for indirect or consequential damages resulting from the use or

application of this information.

The illustrations, charts, and examples shown in this document are

intended solely to illustrate the principles of programmable

controllers and some of the methods used to apply them. Particularly

because of the many requirements associated with any particular

application, Allen-Bradley Company cannot assume responsibility or

liability for actual use based upon the illustrative uses and applications.

No patent liability is assumed by Allen-Bradley Company with

respect to use of information, circuits, equipment, or software

described in this text.

Reproduction of the contents of this document, in whole or in part,

without written permission of Allen-Bradley Company is prohibited.

Introduction

This application note demonstrates how to transfer ASCII data to an

SLC 5/02 or later processor by using a remote SLC 500 BASIC

module. An example shows how to transfer a maximum of 10

ASCII characters to an SLC 5/03 processor.

General Information

M-files cannot be accessed from a module in a remote I/O chassis.

Therefore, the BASIC module (Catalog Number 1746-BAS) is

limited to its 8 input and 8 output image words for data transfer

between itself and the SLC 5/02 or later processor. The first three

words of the I/O image are reserved for handshake bits, status, and

character count respectively. So, only 5 input and 5 output words are

available for actual data transfers. In addition, since a total of 8

words of image are used, they must be block transferred because

they do not fit in the image allocated in the Remote I/O Adapter

module (Catalog Number 1747-ASB).

To keep the BASIC programming to a minimum and the throughput

to a maximum, CALL 22 is used to transfer data from PRT1 on the

BASIC module to the SLC 5/03 processor in this case. CALL 22

operates on an interrupt basis, so the throughput of data from PRT1

to the backplane is 10 ms or less. To calculate overall throughput for

your specific system, consult your Remote I/O Adapter User Manual

(Publication 1747-6.13) and your Remote I/O Scanner User Manual

(Publication 1747-6.6).

If you also wish to transfer data www.abb-drive.com from a SLC 5/02 or later processor

to a BASIC module in a remote I/O chassis, please refer to the

BASIC Language Reference Manual (Publication 1746-6.3) and

refer to the section on CALL 23.

Description of the Application Example

This application example transfers up to 10 ASCII characters to the

SLC 5/03 processor. Each data packet less than 10 characters must

be terminated with a carriage return character (13 decimal) in order

to alert the BASIC module to transfer the data to the backplane. This

termination character may actually be any unique character. If you

require a different termination character, simply replace the “13” in

line 150 of the BASIC program with the decimal equivalent of the

new termination character.