Autronica Maritime gas alarm control panel kit BS-420MG
Autronica BS-420MG Features
Autronica SD Card Replacement in BC-420. BS-420.BS-430. BU-BV-420
SD Card Replacement in BC-420. BS-420.
BS-430. BU-BV-420
Preparing for replacement
Use an antistatic wrist strap
Disconnect the mains power and battery backup
Open the front panel
Unscrew the 4 wing nuts, disconnect all cables (both
ribbon cables, Ethernet cable if used)
Remove the front panel and place it horizontally on a
table with the yellow label facing upwards
Tear of the yellow label in order to access the cut out
and the SD Card (see picture)
Replace the SD Card (see detailed description on next
page)
Place the new yellow label at the same location as the
previous one
Reassemble the front panel, tighten the 4 wing nuts,
then reconnect all cables that have been
disconnected
Close the front panel
Autronica SD Card Replacement in BC-440
SD SD Card Replacement in BC-440
Preparing for replacement
Use an antistatic wrist strap
Disconnect the mains power and battery backup
Unscrew the 4 screws on the BC-440 unit
Remove the BC-440 board, disconnect the network
cables, mains cable and AlCom+, plus AFB and serial
contacts if necessary
Consult the drawings below
Identify the version of the Controller board, either
BSA-400 or BSA-400A (see next page)
Make sure you have the correct type of SD Card
according to the version of Controller board (see “SD
Card part numbers” on next page)
Unscrew and remove the 6 screws on the BSF-440
board
Gently place the board beside the unit without
disconnecting the ribbon cable
Replace the SD Card (see detailed description on next
page)
Re-place the BSF-440 board correctly onto the screw
pillars, then mount and tighten the screws
Re-place the BC-440 unit, reconnect all cables that
have been disconnected, then mount and tighten the
4 front screws
Perform a startup (see “Startup” on next page)
Autronica Operator panel BS-430G2
Autronica Controller rack unit BC-440G2
Autronica Controller BC-420G2
The controller serves as a connection unit for the detection loop,
alarm sounders, controls and inputs.
The controller can accommodate up to a maximum of 12 modules.
The system offers a loop driver module for detection loops and several
types of I/O modules (see optional modules below).
A maximum of 6 loop driver modules connected to each controller.
All modules are easily plugged onto each other on a standard mounting
rail inside the unit. The controller provides connections for 2 Ethernet
ports and 2 USB host ports, and communicates with other system units
on the Ethernet-based local area network, AutroNet.
For engineering purposes, we have established kits to be equipped
according to specifications.
The controller kit includes a cabinet with a panel front, power supply module,
communication module and text foils in a chosen language.
Additionally the cabinet can be stacked with
Loop driver module BSD-310
Loop driver module H.P. BSD-311
BS-100 loop driver module BSD-330
Output module BSB-310A
Output module BSJ-310
Input module BSE-310
Input module BSE-320
An Al_Com+ stack can contain up to six loop driver modules (BSD-3xx).
By using AutroFieldBus, an additional Al_Com+ stack (with up to six additional
loop driver modules) can be added to the system.
NOTE! The AutroSafe panels are certified with the Al_Com+ modules mounted
inside the panel cabinet.
Part numbers:
116-BC-420 Controller kit
116-BC-420G2 Controller kit approved acc. to IEC 61508 SIL2