DEIF MVR-T216 Transformer Differential Protection
The MVR-T216 transformer protection offers easy-to-use differential protection
together with overcurrent protection for both high and low voltage side of the
transformer.
The MVR-T216 transformer protection relay provides overcurrent protection for
both low voltage and high voltage side of the transformer. In addition to that it
offers earth fault protection, negative sequence overcurrent protection as well
as two independent instances of restricted earth fault protection for utmost
protection of the transformer.
10x Current input (configurable 0.2…10A)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2 x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– 2 extension slots for additional hardware options
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
– 2nd and 5th harmonic blocking.
– Automatic verification for the connection group and nominal value settings.
– Overloading and through fault statistics for preventive maintenance.
DEIF MVR-T215 Protection Functions
DEIF MVR-T215 Transformer Protection
The MVR-T215 transformer protection relay is a combined monitoring and protection
relays to ensure best performance and availability of a transformer.
The MVR-T215 transformer protection relays comes with current and voltage based
protection functions. The device monitors all relevant measuring values and provides
information for analysis and preventive maintenance. Furthermore it provides the
possibility for automatic and manual voltage regulation and can be used as a back-up
protection.
5x Current input (configurable 0.2…10A)
4x Voltage input (1.00…480.00V (RMS)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2 x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– 3 extension slots for additional hardware options
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
– Overloading and through fault statistics for preventive maintenance.
DEIF MVR-M257 Protection Functions
DEIF MVR-M257 Motor Protection
The MVR-M257 is a motor protection and control solution for large or critical
synchronous and asynchronous motors. It provides voltage and current
based protection functions including differential protection and measurement
of all vital values to be supervised. Furthermore it can connect up to 16 RTD
sensors for thermal alarms and tripping. It comes with 11 avaialable extension
slots to extend the device with additional communication interfaces and I/Os.
10x Current input (configurable 0.2…10A)
4x Voltage input (1.00…480.00V (RMS)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– 9 extension slots for additional hardware options
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
– supports 5 thermal models (time constant accurate)
– soft-start protection starts at 6Hz
– Wye-delta started motor supervision
– two-speed motor protection
– Measuring accuracy can be calibrated to Class 0.2
– Differential Protection
– Synchronous or asynchronous motors
DEIF MVR-M255 Protection Functions
DEIF MVR-M255 Motor Protection
The MVR-M255 is a motor protection and control solution for large or critical
synchronous and asynchronous motors. It provides voltage and current based
protection functions and measurement of all vital values to be supervised.
Furthermore it can connect up to 16 RTD sensors for thermal alarms and tripping.
It comes with 11 avaialable extension slots to extend the device with additional
communication interfaces and I/Os.
5x Current input (configurable 0.2…10A)
4x Voltage input (1.00…480.00V (RMS)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– 11 extension slots for additional hardware options
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
– supports 5 thermal models (time constant accurate)
– soft-start protection starts at 6Hz
– Wye-delta started motor supervision
– two-speed motor protection
– Measuring accuracy can be calibrated to Class 0.2
– Synchronous or asynchronous motors
DEIF MVR-M215 Protection Functions
DEIF MVR-M215 Motor Protection
The MVR-M215 is a motor protection and control solution for large or critical
motor applications. It provides voltage and current based protection functions
and measurement of all vital values to be supervised. Furthermore it can
connect up to 16 RTD sensors for thermal alarms and tripping.
5x Current input (configurable 0.2…10A)
4x Voltage input (1.00…480.00V (RMS)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– 3 extension slots for additional hardware options
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
– supports 5 thermal models (time constant accurate)
– soft-start protection starts at 6Hz
– Wye-delta started motor supervision
– two-speed motor protection
– Measuring accuracy can be calibrated to Class 0.2