Product Description
The SX controller primary function is to execute control
modules that are designed to meet the specific control
requirements of the plant. These control modules use process
signals from the controller’s I/O subsystem and provide
communication of process data to the rest of the DeltaV
control system for operator interaction and data collection.
Each controller node can be installed as a simplex or redundant
node. The controllers are connected to the I/O carriers,
which are mounted to the right of the controller carriers.
Up to 8 carriers with 8 cards each can be connected to the
local bus I/O, for a total of 64 traditional I/O cards. In addition
to the 8 local I/O carriers, each controller can communicate
with an additional 16 Remote I/O units hosting traditional
card based I/O.
In addition to traditional I/O cards, the local bus supports
fieldbus technologies, including Foundation fieldbus, Profibus DP,
DeviceNet and AS-i protocols. The I/O subsystem also supports
Serial interface cards as well as the Ethernet I/O interface.
These various I/O products provide a wide range of interfaces
to meet the needs of your control application.
The SX controller also supports CHARMs and WirelessHART I/O
cards. The CHARM I/O Card (CIOC) connects via the redundant
Ethernet ports of the controller to provide a highly distributed
and flexible I/O solution www.abb-drive.com called Electronic Marshalling. Up to
16 CIOC’s can communicate to one controller, each providing
up to 96 individually configurable signal types.
The capacity limits of the SX controller may vary depending on
the particular application, amount of CHARM I/O Signals and
as well control performance requirements. Enhanced memory
handling and hardware alerts covering capacity and memory,
via indexes, got added to the diagnostic information of the
SX Controller.